Copeland Hermetic Scroll Refrigeration Compressor ZR36KH-PFJ-522
Copeland ZR36KH-PFJ-522 Scroll Compressor: Three Fields That Close, One Label That Does Not, and a Borrowed Description
Key facts at a glance
| Field | Value as printed | Status |
|---|---|---|
| Model | ZR36KH-PFJ-522 | printed |
| Refrigerant | R22 | printed twice on the page |
| Cooling capacity | 30300 Btu/h | printed |
| Input power | 2730 W | printed |
| Supply | 220 to 240 V, 50 Hz, single phase | printed |
| Coefficient of performance | 3.25 | printed, and independently reproducible |
| Nominal size | 3 HP | printed |
| Displacement | 49.5, unit printed as m3/hr | printed, with a unit that cannot be right |
| Net weight | 30.4 kg | printed |
| Cooling capacity in watts | 8880 W | computed from the printed Btu figure |
| Nominal tonnage | 2.5 ton | computed from the printed Btu figure |
Two of the printed rows need work before they can be used, and both are handled below rather than silently corrected.
What the page prints, field by field
The page carries a numbered summary and a detail table. The summary prints five lines and the detail table prints nine rows, and the five overlap completely, so the two agree wherever they can be compared.
| Row | Summary line | Detail table |
|---|---|---|
| Model | ZR36KH-PFJ-522 | ZR36KH-PFJ-522 |
| Refrigerant | R22 | R22 |
| Capacity | 30300 Btu | 30300 Btu |
| Input | 2730 W | 2730 W |
| Voltage | 220 to 240 V, 50 Hz, 1 phase | 220 to 240 V, 50 Hz, 1 phase |
| Nominal | not printed | 3 HP |
| Displacement | not printed | 49.5 m3/hr |
| Coefficient | not printed | 3.25 W |
| Net weight | not printed | 30.4 kg |
Three of the detail rows deserve comment. The coefficient is printed with a unit, and coefficient of performance is dimensionless, so the W is a drafting slip on a field whose value is otherwise confirmed below. The displacement is printed as a volumetric flow rate when the number itself is a swept volume per revolution, which a later section tests. The nominal size is printed as horsepower, a trade label rather than an engineering quantity.
The page also prints an application line naming air conditioning, driers, refrigeration and chillers. It ends in the words and so on, so it is a category phrase rather than a qualification of this model.
The three-field closure: 30300, 2730 and 3.25
Three printed fields can be checked against each other with one conversion.
| Step | Operation | Result |
|---|---|---|
| Capacity in watts | 30300 divided by 3.412 | 8880 W |
| Coefficient | 8880 divided by 2730 | 3.25 |
| Tonnage | 30300 divided by 12000 | 2.5 ton |
The computed coefficient matches the printed 3.25 exactly, to the two decimal places the page publishes. That is a meaningful result rather than a coincidence: it means the capacity, the input power and the coefficient on this page come from one consistent set of numbers. A page assembled from three unrelated sources, which happens often enough in this trade, would not close like this.
The closure does not tell us what test condition produced the numbers. The page prints no condition line, so the coefficient is reproducible from the page but not traceable to a bench. For quotation purposes that is enough. For a design calculation that will be checked against a certified rating, it is not, and the standards section explains which document would settle it.
A second set of listings closes the same rating
Independent listings for the same string print a capacity of 30200 Btu/h and a watt figure of 8850. Those two numbers close against each other to within one watt.
| Quantity | Source | Value |
|---|---|---|
| Capacity | distributor listings | 30200 Btu/h |
| Capacity converted | 30200 divided by 3.412 | 8851 W |
| Watt figure as listed | distributor listings | 8850 W |
| Gap between the two | computed | 1 W |
| Capacity as the product page prints it | product page | 30300 Btu/h |
| Difference between the two capacities | computed | 0.33 per cent |
A one-watt gap on a figure near nine kilowatts is a rounding step, not a disagreement. The 0.3 per cent capacity difference between 30200 and 30300 is the same story on a coarser scale: it is what happens when one table is rebuilt at a different rounding than another.
The energy efficiency ratio that distributors publish for this class of compressor is derived from those numbers rather than measured separately. Dividing 30200 by the printed input power of 2730 gives 11.06, which is published as 11.1. Dividing 11.1 by 3.412 returns 3.25, which is the coefficient the product page prints. So the American convention and the metric convention are the same rating written twice, and the harder of the two numbers to fabricate is identical in all three sources.
This matters for a buyer comparing quotations. A supplier quoting an efficiency ratio and a supplier quoting a coefficient are not offering different performance. They are using different arithmetic on the same measurement, and the conversion is exactly 3.412.
One caveat belongs with this section rather than in a footnote. These distributor figures were read from search results and the listings behind them do not publish a stable product address, so they are recorded here as corroboration and not as a citation. Every one of them is used only where it closes against the product page arithmetic shown above. Before any of them goes into a quotation, re-check it against a live listing, because a figure that cannot be pointed at cannot be defended.
The displacement field carries the right number and the wrong unit
The page prints a displacement of 49.5 with the unit m3/hr. A scroll compressor's displacement is a swept volume per revolution, measured in cubic centimetres per revolution, and 49.5 m3/hr would be a machine of a completely different size. The number is right and the unit is wrong, and the proof takes one multiplication.
| Step | Operation | Result |
|---|---|---|
| Swept volume per revolution | as the product page prints it, read in cm3/rev | 49.5 cm3/rev |
| Volumetric flow at a nominal running speed | 49.5 multiplied by 2900 rpm, converted to hours | 8.61 m3/h |
| Speed implied by the two published figures | 8.61 m3/h divided by 49.5 cm3/rev | 2900 rpm |
The middle row is the test. A distributor listing for the same string prints a displacement of 8.61 m3/h. Multiplying the page's 49.5 by a 2900 rpm running speed reproduces 8.61 m3/h, and running the division backwards from the distributor figure returns the same speed. Two fields from two sources agree once the unit is fixed.
That 2900 rpm is an inference from the two published numbers, not a figure either source states. It is worth keeping labelled as such: it is consistent with a two-pole machine on a 50 Hz supply running slightly below synchronous speed, which is where a scroll compressor of this size normally sits.
The correct reading is therefore 49.5 cm3/rev, and 8.61 m3/h is that swept volume converted to a flow at a nominal running speed. Anyone who quotes 49.5 m3/hr in a specification would overstate the machine by three orders of magnitude.
What the 36 in ZR36KH means
Copeland's ZR numbering carries a nominal capacity in thousands of British thermal units per hour, referred to the 60 Hz rating basis, and the printed capacity on this page is a 50 Hz figure.
| Quantity | Value | Relation |
|---|---|---|
| String code | 36 | nominal capacity basis, thousand Btu/h |
| Implied 60 Hz nominal | 36000 Btu/h | the code read directly |
| Printed 50 Hz capacity | 30300 Btu/h | as printed on the page |
| Ratio of printed to nominal | 0.842 | computed |
| Speed ratio, 50 to 60 Hz | 0.833 | computed |
| Excess over pure speed scaling | 1.0 per cent | computed |
The printed capacity sits just above what pure speed scaling would predict. That is the expected direction, because volumetric efficiency falls as speed rises, so a machine run slower gives up slightly less capacity than the speed ratio alone implies. A ratio of 0.842 against 0.833 is exactly the small positive gap that behaviour produces.
This is why the code should never be read as a 50 Hz rating. Code 36 does not mean 36000 Btu/h on a 50 Hz supply; it means the nominal class, and the 50 Hz figure is 30300 Btu/h. Converting that gives 2.5 ton, not 3 ton, so the tonnage label and the code differ by a whole class.
Is this a refrigeration compressor?
The string is often described as a refrigeration compressor. Tested against the sources, that description is too loose.
What the sources support: this is the ZR platform, the medium and high temperature line, and its published ratings are air conditioning ratings. The working condition printed on distributor listings for this string is the 7.2 and 54.6 degree pair that the trade uses for air conditioning ratings. Copeland's own product selector keeps air conditioning and the three refrigeration temperature bands as separate application values, which is the manufacturer drawing the same distinction this section is drawing.
What the same catalogue shows about actual refrigeration: the low temperature work is carried by different prefixes. The Copeland scroll compressor category on this site titles its refrigeration listings with the words low temperature refrigeration and files them under ZMD, ZM and ZXI strings, none of which is this model.
| String | Title as the category page prints it | Platform role |
|---|---|---|
| ZR36KH-PFJ-522 | not listed under a low temperature title | medium and high temperature, air conditioning ratings |
| ZMD26KVE-TFD-284 | Copeland Scroll Low Temperature Refrigeration Compressor | low temperature refrigeration |
| ZMD26KVE-TFD-274 | Copeland Scroll Low Temperature Refrigeration Compressor | low temperature refrigeration |
| ZM18K4E-TFD-977 | Copeland Scroll Low Temperature Refrigeration Compressor | low temperature refrigeration |
| ZXI21KCE-TFD-557 | Copeland Scroll Low Temperature Refrigeration Compressor | low temperature refrigeration |
So the accurate sentence is that this model is a medium and high temperature scroll compressor whose primary duty is comfort cooling, and which can serve refrigeration loads that sit above freezing. Calling it a refrigeration compressor without that qualifier invites a buyer to size it for a frozen-goods duty it was never rated for.
The description on the page belongs to another series
This is the most damaging defect on the page, and it is worth naming because it is invisible to a buyer who reads only the table.
The descriptive text above the table describes vapour injection technology, an injection drive valve, ratings from 4 to 8 HP, and a refrigerant set of R404A, R507, R448A, R449A and R465A, and it names the ZFKVE series three times. None of that applies to a ZR36 string: this model is R22, single phase, 3 HP nominal, and has no vapour injection.
The text is boilerplate carried over from a low temperature injection series. Its presence means a reader who takes the prose as a description of this model will believe they are buying a variable-capacity low-GWP injection compressor, which they are not. The table is the only part of the page that describes this string, and this article is built on the table for that reason.
Two smaller defects sit alongside it. The page prints the coefficient with a watt unit, and it prints the displacement with a flow-rate unit, both of which are handled above.
There is also a navigation defect worth knowing about, because it affects how buyers find the part at all. The site's Copeland hermetic compressor collection sits in the reciprocating branch of the catalogue rather than the scroll branch, so a buyer who searches the phrase hermetic Copeland compressor lands on a family this model does not belong to. The scroll branch is the correct entry point for a ZR string.
How to write the purchase order
Pin the full string. ZR36KH-PFJ-522 carries a motor code and a bill-of-material suffix, and the same nominal size exists in other configurations whose suffixes are not interchangeable.
Pin the gas: R22. The page prints it in both the summary and the table, and no alternative appears.
Pin the supply: single phase, 220 to 240 V, 50 Hz. The bracket matters, because a 220 V nameplate and a 240 V supply are different operating points and the field is printed as a range.
Then state the displacement correctly, as 49.5 cm3/rev, and if a volumetric flow is wanted, as 8.61 m3/h at nominal running speed. Never carry the page's unit forward.
Finally, ask for two documents the page does not provide: the capacity and power at the 60 Hz basis, and the condition pair behind the printed rating. Both matter if the machine is going into a system designed around a certified figure.
The rest of the scroll range sits on the wider scroll compressor range page, and the semi-hermetic Copeland pages are the right starting point if the duty turns out to be beyond a hermetic scroll. The full product index carries both branches.
Standards, approvals and where the official data lives
The component standard is IEC 60335-2-34, the part written for sealed motor-compressors. Its current edition scopes single-phase motor-compressors up to a rated voltage of 250 V, which covers a 220 to 240 V single phase machine with margin, and it states that a motor-compressor tested to it does not need the appliance-level motor-compressor tests repeated in the appliance.
The appliance standard is IEC 60335-2-40, the part written for electrical heat pumps, air conditioners and dehumidifiers, and it does not take into account refrigerants other than groups A1, A2L, A2 and A3 as defined by ISO 817. Which of those groups a given R22 charge falls into is settled by the refrigerant safety data sheet supplied with the order, and no source read for this article states it.
The refrigerant designation system is ANSI/ASHRAE Standard 34, which treats R22 as a single-compound refrigerant rather than a blend. That is why the charging advice for this model is simple: a single compound does not fractionate, so a top-up does not change the composition of the charge.
The rating convention used to compare this model against another is set by the industry's own standards body, which maintains the performance rating standards for the HVACR industry. The working condition pairs quoted for this string come from that rating practice rather than from the product page.
For the figures the page does not print, the manufacturer's own data is the only acceptable substitute. The Copeland scroll compressor page is the manufacturer's overview of the platform, and the Copeland Online Product Information tool is its selection and technical data service, which exposes product type, application temperature band, phase, refrigerant and voltage range as separate filters. For a specific model row, the publications and bulletins index on that same service is where the official engineering manuals live.
The commercial frame is the same as for every other compressor in this catalogue. The IEA's work on cooling records how much of the electricity used in buildings goes to air conditioning, which is why the 3.25 coefficient matters more than the 3 HP label.
Frequently asked questions
What capacity does ZR36KH-PFJ-522 have?
30300 Btu/h as printed, which converts to 8880 W and 2.5 ton. Distributor listings print 30200 Btu/h, 0.33 per cent lower, and that figure converts to 8851 W against a listed 8850.
What is the coefficient of performance?
3.25, printed on the page and reproducible from the capacity and input power. Distributors publish an efficiency ratio of 11.1 for the same rating, which is 11.06 before rounding and converts back to 3.25.
Is the displacement 49.5 m3/hr?
No. The number is a swept volume per revolution, so it is 49.5 cm3/rev. Multiplied by a 2900 rpm running speed it gives 8.61 m3/h, which is the figure distributors print.
Is it a refrigeration compressor?
It is a medium and high temperature scroll compressor whose published ratings are air conditioning ratings. Low temperature refrigeration in this catalogue is carried by ZMD, ZM and ZXI strings, and the ZMD18KVE-TFD-977 page is a typical example of how those are titled.
Does it have vapour injection?
No. The vapour injection description on the page belongs to a different series. This model is R22, single phase, 3 HP nominal, with no injection circuit.
What refrigerant does it use?
R22, printed twice on the page. It is a single-compound refrigerant, so charging and topping up do not involve fractionation.
Why does the code say 36 when the capacity is 30300?
Because 36 is the nominal capacity class referred to the 60 Hz basis, in thousands of Btu/h. The printed 30300 Btu/h is the 50 Hz figure, which is 84.2 per cent of the nominal and slightly above the pure speed ratio.
What is the easiest field to get wrong?
The displacement. The printed number is correct and the printed unit is not, so it is the one field that must be retyped rather than copied.
Where can I compare the rest of the range?
The Copeland scroll compressor category lists the refrigeration and air conditioning strings separately, and the wider scroll range page covers the other brands in the same branch. The news index lists the site's model write-ups by brand and by date.
Sources
| Source | Document | Use in this article |
|---|---|---|
| S483 | qishanrcompressor.com product page for Copeland Scroll Compressor ZR36KH-PFJ-522, summary and detail table | model, R22, 30300 Btu/h, 2730 W, 220 to 240 V 50 Hz single phase, 3 HP, 49.5, 3.25, 30.4 kg, and the ZFKVE boilerplate quoted in the defects section |
| S484 | qishanrcompressor.com Copeland scroll compressor category, 1140 items across 143 pages | the ZMD, ZM and ZXI strings and their low temperature titles, and the branch positions of the hermetic and semi-hermetic collections |
| S485 | Independent distributor listings for ZR36KH-PFJ 522 | the 30200 Btu/h capacity, the 8850 W figure and the 7.2 and 54.6 degree condition pair |
| S486 | Copeland, scroll compressors product page | the manufacturer overview of the platform used in the standards section |
| S487 | Copeland Online Product Information tool, including the publications and bulletins index | the application temperature bands, the product type filters, and where the official manuals are published |
| S488 | AHRI, standards and guidelines | the performance rating standards body behind the condition pairs |
| S489 | IEC 60335-2-34:2024 and IEC 60335-2-40:2024, IEC webstore | the component scope to 250 V single phase, and the refrigerant grouping clause |
| S490 | ANSI/ASHRAE Standard 34 designation practice, and IEA, The Future of Cooling | R22 as a single compound, and the building electricity share |