GMCC SAVC060D11ULKC scroll compressor
GMCC SAVC060D11ULKC Scroll Compressor: Four Parameter Blocks That Close, One Suffix That Does Not, and No Speed to Quote
Key facts at a glance
| Field | What the block prints | Status |
|---|---|---|
| Model | SAVC060D11ULK | printed on the page; the C form is discussed below |
| Refrigerant | R410A | printed |
| Displacement | 60 cm3/rev | printed |
| Cooling capacity | 19760 W | printed |
| Cooling capacity, second unit | 67421 Btu/h | printed on the same block |
| Power input | 6050 W | printed |
| Coefficient of performance | 3.27 W/W | printed, and independently reproducible |
| Height | 434 mm | printed |
| Supply | DC | printed, with no voltage level |
| Application | air conditioning | printed |
| Tonnage | 5.62 ton | computed from the printed Btu figure |
| Capacity per swept cm3 | 329.3 W | computed from two printed fields |
The two computed rows are worked in full below, because they are the cheapest test of whether the block was transcribed correctly.
What the page prints, field by field
The block is a two-column table with nine rows. Eight of them carry a field name; one does not.
| Row | Field name as printed | Value as printed |
|---|---|---|
| 1 | Model | SAVC060D11ULK |
| 2 | Displ. | 60 cm3/rev |
| 3 | Capacity | 19760 W |
| 4 | none | 67421 Btu/h |
| 5 | Power | 6050 W |
| 6 | Cop | 3.27 W/W |
| 7 | Height | 434 mm |
| 8 | Refrigerant | R410A |
| 9 | Voltage | DC |
| 10 | Usage/Application | air conditioning |
Two defects are visible in that listing and neither is fatal. The Btu row has no field name, so a reader scanning the left column sees one capacity row and misses the second unit entirely. And the voltage row prints DC, which is a current form rather than a supply specification: it tells a buyer the machine takes a direct-current drive and tells them nothing about the voltage class they must provide.
The page also carries a generic scroll-compressor paragraph and four key features: a wide application envelope, IDV technology for part-load efficiency, manifold configurations for staged modulation, and a claim about robustness. The paragraph is the same text on every scroll page in this category, so it describes the platform and not this model. No figure in this article comes from it.
Four blocks close on two independent paths
The 060 block is not an isolated row. Three larger models in the same sub-family print the same nine fields, and all four close twice over: once through the coefficient and once through the unit conversion.
| Quantity | Operation | Printed or computed |
|---|---|---|
| Coefficient | 19760 divided by 6050 | 3.2661, printed as 3.27 |
| Capacity in Btu | 19760 multiplied by 3.412 | 67421.1, printed as 67421 |
| Tonnage | 67421 divided by 12000 | 5.62 ton |
Both computed values land on the printed digits, not near them. The coefficient is 3.2661 against a printed 3.27, which is a rounding to two decimals. The Btu figure is 67421.1 against a printed 67421, which is a rounding to the nearest unit. Four independent blocks behave the same way, which is set out in the ladder section below.
The closure tells us the block is internally consistent. It does not tell us what test condition produced it, because the page prints no condition line at all. That matters and is picked up again under the speed section and again under the purchase order.
The 060 code is the displacement, and the D code is not
The second field of the string varies across the family and does not track displacement, which is worth showing because a buyer will assume it does.
| Code in the string | Printed displacement | D field | Displacement code matches printed value |
|---|---|---|---|
| 060 | 60 cm3/rev | D11 | yes |
| 070 | 70 cm3/rev | D44 | yes |
| 080 | 80 cm3/rev | D63 | yes |
| 096 | 96 cm3/rev | D33 | yes |
On all four models the three-digit code equals the printed displacement in cubic centimetres per revolution, exactly and with no scaling. That is a stronger relationship than the GMCC rotary compressor range shows, where the three digits are a nominal class that only approximately matches the printed swept volume. Here the code can be read directly.
The D field is a different matter. It runs D11, D44, D63 and D33 against displacements of 60, 70, 80 and 96, so it does not rise with capacity and does not fall with it either. It is also independent of displacement within a single size class: the category lists both SAVC070D44ULK and SAVC070D22ULKA at the same 070 displacement code, so the D field changes while the swept volume does not.
No document read for this article defines the D field. It most likely encodes a drive or electrical variant, and that is the limit of what can be said: the article does not decode it and does not guess at it. A buyer who needs the meaning has to get it from the manufacturer, because the naming is not published in the material that was available.
No speed is printed, and for a DC inverter machine that matters
The page calls the machine a DC compressor and the category page titles the whole shelf GMCC Inverter Scroll Compressor. Both are consistent. What neither publishes is a running speed.
That gap is structural rather than careless. On a fixed-speed machine, a swept volume and a supply frequency fix the volumetric flow, and a reader can convert one into the other. On a variable-speed machine there is no single speed to multiply by, so the swept volume fixes a range and not a point. Printing one flow figure would therefore be a choice about which operating point to represent, and the page declines to make that choice.
This article declines too. It does not convert 60 cm3/rev into a volumetric flow, because that conversion would require a speed the sources do not state, and a converted figure would look exactly like a printed one. Any quotation that shows a flow rate for this string is showing a figure from somewhere other than these pages.
The practical consequence for a buyer is that three fields must be obtained before the machine can be specified: the voltage class that the DC input expects, the speed range the drive will deliver, and the condition pair behind the printed capacity and power. All three are absent from the page, and none of them can be inferred from what is present.
The SAVC ladder: what a step up actually buys
The most useful thing the GMCC scroll category does is put four sizes side by side. Read across them, the family behaves like a single design scaled up rather than four different machines.
| Model | Displacement | Capacity | Power | COP | Capacity per cm3 |
|---|---|---|---|---|---|
| SAVC060D11ULK | 60 cm3/rev | 19760 W | 6050 W | 3.27 | 329.3 W |
| SAVC070D44ULK | 70 cm3/rev | 22935 W | 6950 W | 3.30 | 327.6 W |
| SAVC080D63ULK | 80 cm3/rev | 26400 W | 8040 W | 3.28 | 330.0 W |
| SAVC096D33ULK | 96 cm3/rev | 31400 W | 9660 W | 3.25 | 327.1 W |
Capacity per swept cm3 runs 329.3, 327.6, 330.0 and 327.1 across a 60 per cent displacement range. That is a spread of 2.9 W, or 0.9 per cent, which says the four rows are the same thermodynamic design at four sizes. Power per swept cm3 behaves the same way, at 100.8, 99.3, 100.5 and 100.6.
The commercial reading is the useful part.
| Step | Displacement | Capacity | Power | COP |
|---|---|---|---|---|
| 060 to 070 | plus 16.7 per cent | plus 16.1 per cent | plus 14.9 per cent | 3.27 to 3.30 |
| 070 to 080 | plus 14.3 per cent | plus 15.1 per cent | plus 15.7 per cent | 3.30 to 3.28 |
| 080 to 096 | plus 20.0 per cent | plus 18.9 per cent | plus 20.1 per cent | 3.28 to 3.25 |
| 060 to 096 | plus 60.0 per cent | plus 58.9 per cent | plus 59.7 per cent | 3.27 to 3.25 |
Two things follow. First, capacity tracks power almost exactly across every step, so moving up a size buys capacity at essentially no change in efficiency: the coefficient moves between 3.25 and 3.30 across the whole family, a band 1.5 per cent wide. There is no efficiency argument for choosing the smallest frame and running it hard, and no efficiency penalty for choosing the largest.
Second, the height is not a smooth function of size. The 060, 070 and 096 all print 434 mm while the 080 prints 480 mm. A buyer who assumes the mounting envelope grows with capacity will get the 080 wrong, and the page that would correct them is one click away from the one they are reading.
Is this an air conditioning compressor or a refrigeration one?
It is an air conditioning compressor, and the manufacturer's own product tree is the cleanest evidence for that.
The product page prints air conditioning as the application. Above that, GMCC files its scroll line under Commercial AC Compressor, with a sub-category titled Commercial DC Inverter Scroll Compressor, alongside two specialised variants for computer-room units and for energy storage. The freezing and cold storage scroll work sits in a different branch entirely, under Cold and Freezing Field Compressor, with its own sub-category for single stage scroll compressors for freezing and cold storage.
That is not a marketing distinction. It is how the manufacturer separates two product lines with different envelopes, and it means a string filed under the commercial AC scroll category is not interchangeable with one filed under freezing, even where the displacement looks comparable.
The refrigerant points the same way. R410A is the air conditioning gas in this family, and it is not a freezing refrigerant. Any enquiry that describes this model as a refrigeration compressor for a frozen-goods duty is describing a different product.
The wider scroll range page is where the other scroll brands in this branch are listed, if the duty turns out to belong to a different platform.
The final C: where ULKC is printed and where ULK is
This is the one finding that matters before an order is placed, and it is stated plainly because it cannot be resolved from the sources.
| Source | Suffix printed | Whether that source carries a parameter block |
|---|---|---|
| The product page for this machine | ULK | yes, the nine fields used in this article |
| The GMCC scroll category listing | ULK | no |
| The marketplace listing for the same machine | ULK | no, only warranty and shipping terms |
| The site's own news item about a handover | ULKC | no, a delivery note |
| The string supplied for this article | ULKC | not applicable |
The C form is printed in the shop's own handover news item, and the source is named in the sources table below.
So the C form appears, and it appears in the shop's own material, but it never appears next to a parameter block. Every figure in this article therefore belongs to the ULK form, and a buyer who orders a ULKC form on the strength of these numbers is relying on an assumption rather than on a document.
There is a real possibility that the C is meaningful. The same category lists two models at the same displacement code, SAVC070D44ULK and SAVC070D22ULKA, which shows that this naming scheme does carry trailing and mid-string variants that are separately stocked and separately listed. A trailing C could therefore be a genuine variant that has simply not been given a page yet.
There is also a real possibility that it is a typographical extra character in a news headline. The article does not choose between those explanations, because the sources do not.
The practical rule is simple. Quote the full string as printed on the page that carries the parameters, and if the customer's own records say ULKC, ask the customer to confirm which form their equipment was built with before shipping either one.
The news index lists the site's write-ups by brand and by date, which is the quickest way to see whether a variant form has since been given a page of its own.
How to write the purchase order
Pin the identity first, and pin it from the page rather than from the headline. The model as the parameter block prints it is SAVC060D11ULK, with a 060 displacement code and a D11 field.
Pin the gas: R410A. It is printed once and nothing else is offered.
Then accept that four fields are missing and ask for them in writing: the DC voltage class, the speed range, the condition pair behind the capacity and power, and the connection and mounting detail. The page prints a height and nothing else about the envelope, so a buyer fitting this into an existing unit should ask for the drawing rather than infer one.
Finally, treat the tonnage as a derived convenience and not as a rating. The 5.62 ton figure in this article is 67421 Btu/h divided by 12000, which is arithmetic on a printed number, not a manufacturer statement about the machine's class.
The full product index lists both the scroll branch and the rotary branch, so a buyer who is not yet sure which platform a duty needs can start there rather than at a model page.
Standards, approvals and where the official data lives
The component standard is IEC 60335-2-34, the part written for sealed motor-compressors. Its current edition scopes single-phase motor-compressors up to a rated voltage of 250 V and direct-current motor-compressors up to 600 V, which is the clause that matters for a DC machine, and it states that a motor-compressor tested to it does not need the appliance-level motor-compressor tests repeated.
The appliance standard is IEC 60335-2-40, the part written for electrical heat pumps, air conditioners and dehumidifiers, and it does not take into account refrigerants other than groups A1, A2L, A2 and A3 as defined by ISO 817. Which of those groups a given R410A charge falls into is settled by the refrigerant safety data sheet supplied with the order, and no source read for this article states it.
The rating convention used to compare one model against another is set by the industry's standards body, which maintains the performance rating standards for the HVACR industry. That is the framework under which condition pairs are published at all, which is why their absence here is worth flagging rather than shrugging at.
For the figures this page does not print, the manufacturer is the only acceptable substitute. The GMCC product centre is where the commercial scroll line is catalogued, and the GMCC scroll compressor product manual sits on the manufacturer's downloads page, which is the document that would settle the voltage class, the speed range and the condition pair in one place. Neither was read for this article, and no figure here depends on them.
The commercial frame is the same as for every compressor in this catalogue. The IEA's work on cooling records how much of the building electricity stock goes to air conditioning, which is why a coefficient in the 3.2 to 3.3 band is worth more attention than a nominal size label.
Frequently asked questions
What capacity does the 060 block have?
19760 W as printed, which the same block also prints as 67421 Btu/h. Dividing that by 12000 gives 5.62 ton.
Does the arithmetic check out?
Twice over. 19760 divided by 6050 gives 3.2661 against a printed coefficient of 3.27, and 19760 multiplied by 3.412 gives 67421.1 against a printed 67421.
What does the 060 in the model number mean?
The swept volume in cubic centimetres per revolution. All four models in the family match their three-digit code to the printed displacement exactly, which the rotary families in this catalogue do not.
What does the D field mean?
It is not decoded and no source read for this article defines it. It does not track displacement: the same category lists SAVC070D44ULK and SAVC070D22ULKA at the same 070 code, so the field varies independently of size.
Is the displacement 60 cm3/rev the same as a flow rate?
No. A flow rate would need a speed to multiply by, and the page prints no speed because the machine is a variable-speed drive. This article does not convert one into the other.
Is there a C on the end of the model number?
The parameter block, the category listing and the marketplace listing all print ULK. A trailing C appears in the site's own news item about a handover and in the string supplied for this article. No source carrying parameters prints the C form.
Is it an air conditioning compressor?
Yes. The page prints air conditioning as the application, and GMCC files the line under Commercial DC Inverter Scroll Compressor, separate from its freezing and cold storage scroll branch.
Why is the 080 taller than the 096?
Both are in the same family and the 096 carries more displacement, but the 080 prints a height of 480 mm against 434 mm for the 060, 070 and 096. The sources give no reason, so check the drawing rather than the pattern.
Where can I compare the rest of the range?
The GMCC scroll category page carries the full sub-family with parameters, and the wider scroll range page covers the other scroll brands in the same branch.
Sources
| Source | Document | Use in this article |
|---|---|---|
| S491 | qishanrcompressor.com product page for GMCC Scroll Compressor SAVC060D11ULK | the nine printed fields, the unnamed Btu row, and the DC voltage row with no level |
| S492 | qishanrcompressor.com GMCC Inverter Scroll Compressor category, 15 items across 2 pages | the eight listed models, the two sub-families, and the SGAGC and ULKA variants used in the naming sections |
| S493 | qishanrcompressor.com pages for SAVC070D44ULK, SAVC080D63ULK and SAVC096D33ULK | the three sibling blocks behind the ladder, the step-up deltas and the 480 mm height |
| S494 | gmcccompressors.com company news, handover item dated 15 April 2026 | the only printed occurrence of the trailing-C form, and its context as a one-piece aftermarket delivery |
| S495 | made-in-china.com listing for the same machine | the second ULK-form source, and confirmation that the listing carries no parameter block |
| S496 | GMCC product centre, gmcc-welling.com | the Commercial AC Compressor and Cold and Freezing Field branches used in the application section |
| S497 | GMCC downloads page, scroll compressor product manual entry | where the official scroll manual is published, not read for this article |
| S498 | IEC 60335-2-34:2024, IEC 60335-2-40:2024, AHRI standards, and IEA, The Future of Cooling | the 600 V DC scope, the refrigerant grouping clause, the rating framework, and the building electricity frame |
KSG165V1UMT GMCC Rotary Air ConditionerCompressor
GMCC TSM140N1UFT Air Conditioner Compressor
Related Article