GMCC TSM140N1UFT Air Conditioner Compressor
GMCC TSM140N1UFT Air Conditioner Compressor: What the 2024 Catalogue Prints for the R454B Build, and What It Does Not Print
Key facts at a glance
| Field | Value | Where it comes from |
|---|---|---|
| String as supplied | TSM140N1UFT | Buyer request, no prefix added |
| Printed in the 2024 edition | not printed | Full-text scan of all 20 pages |
| Nearest printed string | ASM140N1UFT | Page 12, SM group, R410A fixed-speed block |
| What differs | the first letter: T versus A | Naming rule |
| T means | R454B | Naming rule, refrigerant table |
| A means | R410A | Naming rule, refrigerant table |
| R454B rows in the edition | 23, in the SG, SK, SN, SQ and T-series families | Row scan |
| R454B rows in the SM family | none | Row scan |
| Only R454B row at the 140 code | TSN140D58UFZ, flagged under development | Page 7 |
| Documented R410A row, this tail | 13.9 cm3, 4175 W, 14245 Btu/h, 1355 W, COP 3.08 | Page 12 |
| Supply of that row | 1 phase, 60 Hz, 208 to 230 V | Block header, page 12 |
| Test condition of that row | ASH | Block header, page 12 |
| Body height | 292 mm | Row |
Two of those lines carry the whole argument. The requested string is not in the document, and the displacement printed against the 140 code in this family is 13.9 cm3, not 14.0.
What does the T letter actually change?
The naming rule prints a refrigerant table with fourteen letters. The two that matter here sit two lines apart: A is R410A and T is R454B. Everything after that letter is identical between the two strings, because the series, the displacement code, the power specification and the tail are the same characters in the same positions.
That makes the pair easy to misread. TSM140N1UFT and ASM140N1UFT look like one character apart, and in a catalogue whose rows are dense, a buyer scanning for a number will find a row and stop. The row belongs to the other fluid.
The edition itself treats the distinction as real, not cosmetic. It prints 23 rows whose first letter is T, spread across the SG, SK, SN, SQ and T-series families, and it prints 199 rows whose first letter is A. If the letter were a housekeeping code the two populations would not be separated so cleanly by family, and the T pages would not be headed by their own block labels. They are.
What the edition does not do is print a T row in the SM family. A scan of every model string in the document returns no string beginning TSM, at any displacement. The nearest thing to a bridge is the R454B block at the 140 code, and it is a different family entirely, described below.
What does the printed R410A row say?
The row that the request is modelled on reads, on page 12:
| Displacement | Capacity | Capacity | Input | COP | Capacitor | Height | Suction | Discharge |
|---|---|---|---|---|---|---|---|---|
| 13.9 cm3/rev | 4175 W | 14245 Btu/h | 1355 W | 3.08 | 40/370 | 292 mm | 8.1 mm | 12.9 mm |
Both column closures hold. Capacity over input is 4175 divided by 1355, which is 3.081, printed 3.08. The British thermal figure is the watt figure times 3.412, which is 14245.1, printed 14245. The displacement per second at the block frequency is 13.9 times 60, or 834 cm3 per second, and 1355 W over that volume is 1.625 W per cm3 per second. Capacity per cubic centimetre is 4175 divided by 13.9, or 300.4.
The block header matters as much as the row. It prints R410A, then 1 phase, 60 Hz, 208 to 230 V, then the test condition ASH. Three consequences follow.
First, the capacity is an ASH-condition number. ASH is a harsher rating point than the GX condition used elsewhere on the same spread, which is why this row's coefficient looks low next to its neighbours in the same family. It is not a worse machine; it is a harder test.
Second, the 13.9 figure is what the 140 code means in this family. The same 140 code prints 14.0 cm3 in the SN family, where the rows are a different design. Anyone who reads the code as a displacement and skips the column will be wrong by one tenth of a cubic centimetre per revolution before they start.
Third, the row is fixed-speed, not inverter. The page carries no inverter descriptor in this block, and the capacitor column holds a real value, 40 microfarads at 370 VAC. On an inverter page that column prints a dash.
Four builds at 13.9, and what the condition does to the number
The same 13.9 cm3 displacement appears four times in the edition, all in the SM family, all R410A, and the four printed coefficients run from 2.92 to 4.30. Nothing about the hardware explains a 47 percent spread. The supply and the test condition do.
| String | Supply | Condition | Capacity | Input | COP | Capacitor | Height | Page |
|---|---|---|---|---|---|---|---|---|
| ASM140N1UFT | 1 phase, 60 Hz, 208 to 230 V | ASH | 4175 W | 1355 W | 3.08 | 40/370 | 292 | 12 |
| ASM140V1SFT | 1 phase, 50 Hz, 220/240 V | ASH | 3500 W | 1200 W | 2.92 | 40/370 | 290 | 15 |
| ASM140V1VFT | 1 phase, 50 Hz, 220 to 240 V | GX | 4060 W | 945 W | 4.30 | 35/370 | 292 | 13 |
| ASM140V01VDZE | 1 phase, 50 Hz, 220/240 V | GX | 4060 W | 1110 W | 3.66 | 45/370 | 285 | 17 |
Read the table two ways and it teaches two different lessons.
Across the same condition, frequency is the variable. ASM140N1UFT and ASM140V1SFT are both rated at ASH; the first turns at 60 Hz and prints 4175 W, the second at 50 Hz and prints 3500 W. The ratio is 1.193, so the 60 Hz build delivers 19.3 percent more capacity, which is close to the 1.2 speed ratio the frequency implies. Input rises 12.9 percent over the same step, so the coefficient improves slightly, from 2.92 to 3.08.
Across the same supply, the condition is the variable, and it dominates. ASM140V1VFT and ASM140V1SFT are both 50 Hz single-phase machines in a body of about 290 mm; the first is rated at GX and prints 4.30, the second at ASH and prints 2.92. Same family, same displacement, same supply, 47 percent apart, entirely because the header above the row names a different test point. The input difference is 27 percent for a capacity difference of 14 percent.
That second comparison is the discipline this article is built on. If changing only the test condition moves a printed coefficient by 47 percent, then changing the working fluid cannot be handled by scaling anything. There is no factor to apply, in either direction, from R410A to R454B.
The fourth row is the aluminium-winding variant, and it is included to close a common misreading: same supply, same condition, same capacity as the copper GX build, but 1110 W instead of 945 W and a coefficient of 3.66. Winding material is a real variable, and it is printed, not inferred.
What does the edition print for R454B?
Twenty-three rows carry the T letter. Their families are SG, SK, SN, SQ and the T-prefixed twin-cylinder series; none of them is SM. The blocks they sit in are headed R 454 B in the same typographic position where the other blocks print R 410A or R 32.
Exactly one of those rows sits at the 140 displacement code:
| String | Displacement | Capacity | Input | COP | Height | Flag | Page |
|---|---|---|---|---|---|---|---|
| TSN140D58UFZ | 14.0 cm3/rev | 3935 W | 960 W | 4.10 | 260 mm | under development | 7 |
Its closures hold as well: 3935 divided by 960 is 4.099, printed 4.10, and 3935 times 3.412 is 13426.2, printed 13427. It is a DC inverter build rated at SEER60, in a 260 mm body, and it is marked with the triangle that the edition uses for rows still in development.
So the honest reading of the edition is narrower than a buyer might hope. There is an R454B build at this displacement. It is not the SM family, it is not fixed-speed, it is not rated at ASH, it is 1.9 cm3 larger, and it is not yet a released row. Quoting its 3935 W as the answer to a TSM140N1UFT inquiry would be a four-way mismatch presented as a match.
Why the R410A numbers cannot be carried across
Four reasons, in the order a buyer will hit them.
The capacity is not transferable. R454B is a different fluid with a different volumetric capacity, and the edition prints no conversion between fluids. The four-build table above shows how far a printed coefficient moves when only the test condition changes; a fluid change acts on the same quantity, at the same magnitude, and in a direction the document does not state.
The charge and the pressure envelope are not transferable. The row prints no refrigerant charge, no design pressure and no oil grade for either fluid. Those are the fields a system designer needs first, and the edition prints none of them for this row in either letter.
The approval basis is not transferable. A unit built to the R410A row is an ordinary motor-compressor procurement. If the fluid brings a flammable-refrigerant classification into the appliance, the applicable product-safety part changes, and the charge limit, the enclosure, the labelling and the service instructions change with it. Whether a specific fluid is in that scope is a question for the standard's refrigerant table, not for this article.
The ordering basis is not transferable. TSM140N1UFT is not a catalogue string today. A purchase order written against it has no row to point at, and a supplier asked for it will either substitute or decline; both outcomes are better handled before the order than after.
What a buyer should ask for is therefore not a number but a document: the manufacturer's row for the R454B build of this family at this displacement, with its test condition, its supply, its coefficient and its development status stated. Nothing in this article can stand in for that.
What do the supplier pages print?
The supplier site carries four pages in this family. All four are R410A, and one of them carries a defect worth naming.
| Page | Displacement | Input | Capacity | COP stated | Voltage field |
|---|---|---|---|---|---|
| ASM130N1UDZ | 13 cm3/rev | 1270 W | 3870 W | 4.22 | 220-240 V, 50 HZ, 1PH |
| ASM108D13UFZ | 10.8 cm3/rev | 833 W | 3250 W | 3.95 | 220-240 V, 50 HZ, 1PH |
| ASM89D12UEZ | 8.9 cm3/rev | 676 W | 2650 W | 3.92 | DC INVERTER SINGLE CYLINDER |
| ASM99V1VFZ | 9.8 cm3/rev | 656 W | 2820 W | 4.30 | 220-240 V, 50 HZ, 1PH |
The ASM130N1UDZ page states 3870 W of capacity and 1270 W of input, and then states a coefficient of 4.22. Those three cannot hold together: 3870 divided by 1270 is 3.047, and the edition prints 3.05 for the same pair. The page also prints 15473 Btu/h against a capacity of 3870 W, where the arithmetic gives 13204. Two fields are corrupt on a page whose other two fields match the edition exactly.
The other three pages close. ASM89D12UEZ prints 2650 W and 676 W with a 3.92 coefficient and 9042 Btu/h, both consistent. ASM99V1VFZ prints 2820 W and 656 W with 4.30 and 9622 Btu/h, both consistent. ASM108D13UFZ prints 3250 W and 833 W with 9042-consistent Btu, and a coefficient of 3.95 where its own pair gives 3.90, a small drift rather than a corrupt field.
The voltage field is the other thing to watch. Three pages here carry a real supply, and the inverter page carries the drive name instead, exactly as the inverter pages elsewhere on the site do. So a buyer can read a voltage for a fixed-speed build and cannot for an inverter build.
None of the four pages prints a test condition in its specification block, so a coefficient read from them cannot be placed beside an edition row without first establishing which condition was used. None of these four pages is the requested string, and none of them is R454B. The site's GMCC rotary compressor range page lists the family as a whole, and the GMCC brand index groups every range the supplier carries; neither carries an R454B row at this displacement.
How should a buyer specify an R454B build?
Eight steps, in the order that avoids writing an order against a row that does not exist.
1. Quote both letters explicitly. Write TSM140N1UFT as requested and ASM140N1UFT as the documented neighbour, and say which one the price is for.
2. Do not adopt the R410A row as the R454B specification. The 4175 W, the 14245 Btu/h and the 3.08 belong to ASM140N1UFT at ASH on a 60 Hz supply. They are not a starting point to be adjusted.
3. Ask for the test condition with the capacity. A capacity without its condition is not a specification; the four-build table above shows a 47 percent spread on one displacement.
4. Ask for the supply with the capacity. The same family prints 60 Hz and 50 Hz builds, and the capacity moves with it.
5. Ask whether the build is released. The only R454B row at this displacement is flagged under development, and a developing row is not a purchasing option.
6. Ask for the charge, the design pressure and the oil grade. None of them is printed for this row, and all of them are needed before a system is drawn.
7. Confirm the appliance-safety basis if the fluid brings a flammable-refrigerant classification. That is an appliance-level question, not a compressor-level one, and it should be settled before the compressor is ordered.
8. Keep 8.1 mm suction and 12.9 mm discharge as the piping assumption only after the row confirms it. Those dimensions are printed for the R410A row in this family; a new fluid changes mass flow and may change them.
Where can the row be checked?
Three checks a buyer can run without trusting this article.
The edition. ASM140N1UFT sits on page 12, in the SM group of the R410A fixed-speed column, under a header that prints 1 phase, 60 Hz, 208 to 230 V and the ASH condition. The file is a 20-page PDF of 2,990,900 bytes with an MD5 of 5c58f3bf5681501f481fd8396febc207, and a distributor-hosted copy of the 2024 manual can be downloaded and compared byte for byte. The manufacturer's product centre lists the current range, and the downloads page on the manufacturer site is the official route to the file.
The arithmetic. Every closure in this article is reproducible with a calculator: 4175 over 1355, 4175 times 3.412, 13.9 times 60, and 1355 divided by that product. If the row is revised, the closures move with it and the change is visible.
The absence. A full-text scan for TSM returns nothing, and a scan of model strings returns 23 T rows in other families. That is the check that matters most for this string, and it takes a minute.
Which standards and approvals frame the purchase?
Nothing in the row prints a certificate or a compliance statement, and no claim of certification should be inferred from this article. Four references frame the work a buyer will have to do.
For the component, IEC 60335-2-34, which is the part of the household appliance series written for motor-compressors, is the reference most often named in procurement documents for hermetic compressors. It says nothing about which fluid the compressor may carry.
For the appliance, IEC 60335-2-40, which is the part written for heat pumps and air conditioners using flammable refrigerants, is the part that governs when the fluid brings a flammable classification into the unit. Its scope is set by the refrigerant table in the standard, and a buyer should read that table rather than accept a summary.
For the fluid, R454B is a fluorinated refrigerant like the R410A it is positioned against. Equipment placed on the European market falls under Regulation (EU) 2024/573, the framework that governs fluorinated gases, and the obligations attach to the charge and the operator.
For context, the IEA's The Future of Cooling remains the most cited framing of how cooling demand grows with income and temperature. It is background for a selection decision, not evidence about any compressor.
The wider rotary compressor category page groups the family for readers who want to see where a 13.9 cm3 build sits, and the GMCC scroll line is where a buyer should look only after accepting that scroll numbers do not transfer to a rotary row. An R410A example on the blog side applies the same field-by-field method to a different refrigerant.
Frequently asked questions
Is TSM140N1UFT in the 2024 catalogue?
No. A full-text scan of all 20 pages returns no row for that string, and no string beginning TSM at any displacement. The nearest printed row is ASM140N1UFT, which differs in the first letter.
What does the first letter mean?
It is the refrigerant, per the naming rule's table. A is R410A and T is R454B. Everything after that letter in these two strings is identical, which is what makes the pair easy to confuse.
Can I use the ASM140N1UFT numbers for an R454B build?
No. The 4175 W, the 14245 Btu/h and the 3.08 are R410A figures at the ASH condition on a 60 Hz supply. A different fluid has a different volumetric capacity and a different pressure envelope, and the edition prints no conversion.
Why does the coefficient look low next to other SM rows?
Because the header names ASH rather than GX. On the same spread, a 50 Hz SM build rated at GX prints 4.30 while a 50 Hz SM build rated at ASH prints 2.92. The condition, not the hardware, sets the number.
Is 140 the displacement in cm3?
Not reliably. In the SM family the 140 code prints 13.9 cm3, and in the SN family it prints 14.0 cm3. Read the displacement column rather than the code.
Does the edition print any R454B row at this displacement?
One, and it is a different machine: TSN140D58UFZ, 14.0 cm3, an inverter build rated at SEER60, 3935 W, 960 W, coefficient 4.10, in a 260 mm body, flagged under development.
Is the compressor fixed-speed or inverter?
The documented R410A row is fixed-speed, and its capacitor column holds 40/370. An inverter row in this edition prints a dash in that column instead.
Is there a page for this string on the supplier site?
No. The site index carries four pages in this family, all R410A, none R454B, and none at this string. The edition is the only public document for the row.
What is missing from the row?
Charge, oil grade and charge, design pressure, running current, speed, sound level, locked-rotor current and ingress protection are all absent, for this row and for the R454B rows equally.
Sources
| Reference | Use in this article | Link |
|---|---|---|
| GMCC rotary compressor catalogue, 2024 edition, 20 pages, 2,990,900 bytes, MD5 5c58f3bf5681501f481fd8396febc207 | Rows, block headers, naming rule, the four 13.9 builds | PDF mirror, enstar-hvac |
| GMCC product centre | Current range listing | gmcc-welling.com product page |
| GMCC download list | Official route to the catalogue file | gmcc-welling.com download list |
| IEC 60335-2-34:2024 | Motor-compressor safety standard | webstore.iec.ch |
| IEC 60335-2-40:2024 | Appliance safety for flammable refrigerants | webstore.iec.ch |
| Regulation (EU) 2024/573 | Fluorinated gas framework | eur-lex.europa.eu |
| IEA, The Future of Cooling | Cooling demand context | iea.org report |